Symptom: The Pressure At The Tapping Point Is Temporarily Unusually High; Symptom: Tank Disinfection Function Is Not Completed Correctly (Ah-Error); Solving Problems Based On Error Codes; To Display The Help Text In Case Of A Malfunction - Daikin Altherma 3 WS EWSAH06UD 9W Series Installer's Reference Manual

Hide thumbs Also See for Altherma 3 WS EWSAH06UD 9W Series:
Table of Contents

Advertisement

15.3.7 Symptom: The pressure at the tapping point is temporarily unusually high

15.3.8 Symptom: Tank disinfection function is NOT completed correctly (AH-error)

15.4 Solving problems based on error codes

15.4.1 To display the help text in case of a malfunction

EWSAH/X06UD
Daikin Altherma 3 WS
4P675765-1 – 2022.04
Possible causes
Failing or blocked pressure relief valve.
Possible causes
The disinfection function was
interrupted by domestic hot water
tapping
Large domestic hot water tapping
happened recently before the
programmed start-up of the disinfection
function
The disinfection operation was stopped
manually: [C.3] Operation > Tank was
turned off during disinfection.
If the unit runs into a problem, the user interface displays an error code. It is
important to understand the problem and to take measures before resetting an
error code. This should be done by a licensed installer or by your local dealer.
This chapter gives you an overview of all possible error codes and their descriptions
as they appear on the user interface.
For detailed troubleshooting of each error, see the service manual.
In case of a malfunction, the following will appear on the home screen depending
on the severity:
: Error
: Malfunction
You can get a short and a long description of the malfunction as follows:
15
Troubleshooting
|
Corrective action
Flush and clean the complete tank
including the piping between pressure
relief valve and the cold water inlet.
Replace the pressure relief valve.
Corrective action
Program the start-up of the disinfection
function when the coming 4 hours NO
domestic hot water tapping is expected.
If in [5.6] Tank > Heat up mode the
mode Reheat only or Schedule +
reheat is selected, it is recommended
to program the start-up of the
disinfection function at least 4 hours
later than the last expected large hot
water tapping. This start-up can be set
by installer settings (disinfection
function).
If in [5.6] Tank > Heat up mode the
mode Schedule only is selected, it is
recommended to program a Eco action
3 hours before the scheduled start-up
of the disinfection function to preheat
the tank.
Do NOT stop tank operation during
disinfection.