Table 23. Continuous Operation Specifications for ASHRAE A2
Temperature
Allowable continuous operations
Temperature range for
altitudes <= 900 m (<=
2953 ft)
Humidity percent range
(non-condensing at all
times)
Operational altitude de-
rating
Table 24. Continuous Operation Specifications for ASHRAE A3
Temperature
Allowable continuous operations
Temperature range for
altitudes <= 900 m (<=
2953 ft)
Humidity percent range
(non-condensing at all
times)
Operational altitude de-
rating
Table 25. Continuous Operation Specifications for ASHRAE A4
Temperature
Allowable continuous operations
Temperature range for
altitudes <= 900 m (<=
2953 ft)
Humidity percent range
(non-condensing at all
times)
Operational altitude de-
rating
Refresh rate (Hz)
60
60
60
60
Specifications
10–35°C (50–95°F) with no direct sunlight on the equipment
8% RH with -12°C minimum dew point to 80% RH with 21°C (69.8°F) maximum dew point
Maximum temperature is reduced by 1°C/300 m (1.8°F/984 Ft) above 900 m (2953 Ft)
Specifications
5–40°C (41–104°F) with no direct sunlight on the equipment
8% RH with -12°C minimum dew point to 85% RH with 24°C (75.2°F) maximum dew point
Maximum temperature is reduced by 1°C/175 m (1.8°F/574 Ft) above 900 m (2953 Ft)
Specifications
5–45°C (41–113°F) with no direct sunlight on the equipment
8% RH with -12°C minimum dew point to 90% RH with 24°C (75.2°F) maximum dew point
Maximum temperature is reduced by 1°C/125 m (1.8°F/410 Ft) above 900 m (2953 Ft)
Color depth (bits)
8, 16, 32
8, 16, 32
8, 16, 32
8, 16, 32
Technical specifications