MX480 Universal Routing Platform Hardware Guide
DC Power Cable Specifications for the MX480 Router
MX480 Host Subsystem
58
DC Power Cable Lug Specifications-The accessory box shipped with the router includes
the cable lugs that attach to the terminal studs of each power supply (see
Figure 17 on page
58).
Figure 17: DC Power Cable Lug
End view
0.28
diameter
0.55
each hole
0.08
0.25
0.625
CAUTION:
Before router installation begins, a licensed electrician must attach
a cable lug to the grounding and power cables that you supply. A cable with
an incorrectly attached lug can damage the router.
NOTE:
The same cable lug is used for the grounding cable.
DC Power Cable
Specifications-Table 22 on page 58
the power cables, which you must supply.
Table 22: DC Power Cable Specifications
Cable Type
Quantity and Specification
Power
Eight 6-AWG (13.3 mm
code
2.25
Crimp area
0.37
All measurements in inches
summarizes the specifications for
2
), minimum 60°C wire, or as required by the local
Copyright © 2019, Juniper Networks, Inc.
6 AWG conductor