Chapter 8: Post-installation administration

Enabling alarms to INADS via SNMP

Note:
Do these steps only if a Secure Service Gateway (SSG) is being installed.
Note:
Enable alarms on both media servers on a duplicated system.
1. Start a telnet session.
2. Type almsnmpconf -d ipaddress -c communityname and press Enter, where
ipaddress is the trap receiver address for the SSG device and communityname is the
community string name required by the SSG device.
3. Type almsnmpconf and press Enter.
Verify that the correct information was entered.
4. At the prompt, type almenable -s y and press Enter.
5. Type almenable and press Enter.
Verify that the SNMP alarm origination is enabled. If used, verify that alarm origination via
modem is still enabled.
6. Log off.

Before leaving the site

Provide the default LAN security settings to the customer.
Ensure that the customer knows that remote access to the media server is available only if the
the following services are enabled Maintenance Web Interface Firewall screen:
telnet must be enabled to access Telnet
https must be enabled to access the Maintenance Web Interface
def-sat must be enabled to access the SAT commands
162/udp must be enabled to receive SNMP traps from the UPS and Avaya Ethernet switch