15 Industrial Ethernet Overview

15.1 Device Setup

15.1.1 Set IP Address

When shipped, the device is assigned a default IP address of 192.168.0.1, a default Subnet Mask of 255.255.255.0, and a
default Gateway of 0.0.0.0. To change these defaults, go to Main Menu > System > Communications > Ethernet I/O.
15.1.2 Set the Industrial Ethernet Protocol (Ethernet/IP
PCCC/PROFINET
The Industrial Ethernet communication channel is disabled by default. To enable this channel, go to Main Menu > System >
Communications > Industrial Ethernet > Connection. Select the desired channel: Ethernet/IP, MODBUS, PCCC, or
PROFINET. Only one type of connection can be established at a time.
View information about an established connection from Main Menu > System > Communications > Industrial Ethernet >
Status. Click the desired connection to view details.
This device provides extensive logging for the communication that occurs over the Industrial Ethernet connection. View logs
from either Main Menu > System > Communications > Industrial Ethernet > View Logs or Main Menu > Logs >
Communication Logs > Industrial Ethernet.

15.1.3 Set Trigger Mode

Trigger the iVu using the hardware trigger input line or an internally supplied software trigger, or by toggling a bit over
Industrial Ethernet. To only accept triggers generated through the Industrial Ethernet communication channel, go to Main
Menu > Imager > Trigger, and select Industrial Ethernet Only from the drop-down list.

15.2 Supported Functions

Control the iVu over EtherNet/IP, PCCC, Modbus/TCP, or PROFINET using the input and output data the iVu makes
available as a slave device for those protocols.
The following are some of the device operations that can be performed using input and output values:
Product Change
Teach Enable
Trigger the iVu
Read output indicators (pass, fail, ready, error)
Read counters (pass, fail, system error, missed trigger, frame count, iteration count)
Read sensor results

15.2.1 iVu Input Values

The operation of the iVu can be controlled through input bits and commands.
Register/Input Coil Bits
The following commands can only be executed using bits:
Input Coil Bit
Command
0
Product Change
1
Teach Latch
2
Trigger
15
Command
®
)
Description
Execute a product change (inspection number specified in the "Product Change
Number" 32-bit integer register)
Latch a teach flag. The Teach is executed on the next trigger
Causes the iVu to run the current inspection
Set this bit to 1 to execute the command entered in the Command ID Register