Installing an Avaya MCC1 Media Gateway
4
Route the media gateway GROUND wire to the single-point ground block at the AC load
center and connect.
NOTE:
If the media gateway is located remotely (in a separate room or building), connect the
media gateway GROUND wire to an approved ground.
Repeat connecting each media gateway to the single-point ground block.
5
6
At the AC load center, connect a 10 AWG (#25) (6 mm
block. This ground wire will later be tie-wrapped to the trunk cables and connected to the
Coupled Bonding Conductor (CBC) ground block at the MDF.
The Coupled Bonding Conductor (CBC) wires are installed and terminated in
Media Gateways'' on page
Typical Media Gateway Ground Location
Figure notes
1
2
3
4
3
1
4
First Media Gateway
Additional Media Gateways (if
installed)
2
6 AWG (#40) (16 mm
) Media
Gateway GROUND Wire
Media Gateway Ground Terminal
Block
141.
3
2
4
AC Load Center Single-Point Ground
5
6
Less than 50 Wire feet (15.2 m)
10 AWG (#25) (6 mm
7
to CBC
October 2002
2
) wire to the single-point ground
7
3
5
6
2
4
widmgrnd LJK 092697
2
) Ground Wire
''Cabling