4.2.2

CANopen object directory

CANopen object directory
When the drive objects are initialized,
the CANopen objects are initialized in the object directory of the SINAMICS drive line-up
(CANopen slave software).
Objects
The following SINAMICS objects are involved in communication:
1. Control Unit communication objects independent of the drive
2. Drive-dependent communication objects
3. Manufacturer-specific objects
4. Drive objects in drive profile DSP 402
Drive functions
Function Manual, 10/2008, 6SL3097-4AB10-0BP0
– include: Number and number of errors, communication addresses etc.
– Up to eight PDOs for sending and eight PDOs for receiving can be parameterized for
the drive. Each PDO contains:
- Communication and
- mapping parameters (max. 8 bytes/4 words/64 bits)
– Objects to access SINAMICS parameters.
– Free objects for sending/receiving process data, there are freely interconnectable
objects available for each drive object (max. 16) in the object directory (see CANopen
Manual for table).
– The manufacturer-specific range starts in the object directory from address 2000 hex
and ends at 5FFF hex.
– Profile Velocity Mode.
– Setpoint and actual values and comparisons.
Commissioning with CANopen
4.2 Commissioning
71