Communication Board Cbc10 For Canopen - Siemens SINAMICS S120 Commissioning Manual

Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

3.1.3.4

Communication Board CBC10 for CANopen

Table 3- 36
Meaning of the LEDs on the Communication Board CAN CBC10
LED
Color
OPT on the
Control Unit
Green
Red
Commissioning Manual
Commissioning Manual, (IH1), 01/2012, 6SL3097-4AF00-0BP2
Status
OFF
Electronics power supply is missing or outside permissible
tolerance range.
Communication Board either defective or not inserted.
Continuous
OPERATIONAL
light
Flashing
PREOPERATIONAL
light
No PDO communication possible
Single flash STOPPED
Only NMT communication possible
Continuous
BUS OFF
light
Single flash ERROR PASSIVE MODE
The error counter for "error passive" has reached the
value 127. After the SINAMICS drive system was booted
no further active CAN component was on the bus.
Double
Error Control Event, a Guard Event has occurred
flash
Description, cause
Diagnostics
3.1 Diagnostics via LEDs
Remedy
Check baud rate
Check cabling
Check baud rate
Check cabling
Check connection to
CANopen master