8.7.5

Information pertaining to component replacements

Replacing components
Observe the instructions with regard to changes to software components or to changes to
these in the chapter "Safety instructions"!
1. The faulty component was replaced in accordance with safety regulations.
2. Make sure that everybody has cleared the danger zone and then power up the machine.
3. Error F30711 is output with fault value 1031 (data transfer error after replacement of a
4. With STARTER:
5. Without STARTER:
6. Back up all parameters.
7. Perform a POWER ON at all components.
8. Faults F01650/F30650 (acceptance test required; see "Acceptance test and acceptance
9. Before anyone is allowed to enter the danger zone again and before operation is
8.7.6

Information pertaining to series commissioning

A commissioned project that has been uploaded to STARTER can be transferred to another
drive unit including the existing safety parameterization.
1. Download the STARTER project to the drive unit.
2. The alarms F01650/F30650 (acceptance test required) are output.
3. Click "Acknowledge hardware replacement" in the start screen of the safety functions.
4. Save all parameters to the non-volatile memory.
5. Perform a POWER ON at all components.
6. Before anyone is allowed to enter the danger zone again and before operation is
Drive functions
Function Manual, 10/2008, 6SL3097-4AB10-0BP0
WARNING
Sensor Module).
– Click "Acknowledge hardware replacement" in the start screen of safety functions.
– Start the copying function for Node Identifier (p9700 = 1D hex)
– Confirm the hardware CRC on the drive object (p9701 = EC hex)
report") are output.
resumed, select the STO function once and briefly move the drives affected by the
component replacement in plus and minus direction (+/-) with activated safety monitoring
function (SLS, if parameterized) in order to verify proper functionality.
These fault alarms can be acknowledged because a full acceptance test is not required if
no changes were made to safety function parameters.
resumed, select the STO function once and briefly move the drives affected by the
Safety Integrated Functions
8.7 Commissioning
355