General information for commissioning
1.4 Temperature sensors for SINAMICS components
The parameterization of the motor temperature evaluation via the sub D socket X520 must
be performed in the expert list as follows:
● p0600[0..n]: Selection of the encoder (1 or 2) to which the SMC30, that is used for the
● p0601[0..n] = 10 (evaluation via several temperature channels), n = motor data set.
● p4601[0..n]: Select the temperature sensor type for temperature channel 2 (depends on
For multiple temperature channels (use of temperature channels 1 and 2 on SMC30),
parameter r0035 shows the maximum temperature.
Example:
A KTY temperature sensor is connected at the sub D socket X520 on the SMC30 of Encoder
1.
This is parameterized via:
● p0600[0..n] = 1 / p0601[0..n] = 10 / p4601[0..n] = 20
Both temperature channels (X520 and X531) can be used at the same time. In addition to
the above parameterization, the sensor type of the temperature sensor connected at terminal
X531 must be entered in p4600[0..n]. The maximum value is then generated for the motor
temperature and displayed in r0035.
SME20
Parameterization of the evaluation of KTY and PTC temperature sensors, connected at
connector X100, can be performed using the STARTER screen (\Signals and monitoring \
Motor temperature).
CU305
A temperature sensor can also be connected to this module using terminal X133 or sub D
socket X23.
The parameterization of the motor temperature evaluation via the sub D socket X23 or
terminal X133 can be performed using the Starter screen (\Signals and monitoring \ Motor
temperature).
It is not possible to use both temperature channels (X23 and X133) at the same time. Both
channels are connected with each other. The sensors would be connected in parallel and the
temperature display would show the wrong value.
Faults and alarms
F07011 drive: Motor overtemperature
KTY sensor:
The motor temperature has exceeded the fault threshold (p0605) or the timer stage (p0606)
after the alarm threshold was exceeded (p0604) has expired.
This results in the reaction parameterized in p0610.
PTC sensor:
The response threshold of 1650 Ohm was exceeded and the timer stage (p0606) has
expired.
This results in the reaction parameterized in p0610.
If an SME Module is used (p0601 = 10), parameter r0949 displays the number of the sensor
channel that has triggered the message.
34
temperature evaluation, is assigned (n = motor data set).
encoder data set n, not motor data set).
Function Manual, 10/2008, 6SL3097-4AB10-0BP0