3.3.1

Important functions via BOP20

Description
Using the BOP20, the following functions can be executed via parameters that support you
when handling projects:
● Restoring the factory settings
● Copy RAM to ROM
● Acknowledge error
Restoring the factory settings
The factory setting of the complete device can be established in the drive object CU.
● p0009 = 30
● p0976 = 1
Copy RAM to ROM
You can initiate the saving of all parameters to the non-volatile memory in the drive object
CU:
● Press the P key for 3 seconds,
● p0009 = 0
● p0977 = 1
Acknowledge error
To acknowledge all the faults that have been rectified, press the Fn key.
Drive functions
Function Manual, 10/2008, 6SL3097-4AB10-0BP0
or
NOTICE
This parameter is not accepted if an identification run (e.g. motor identification) has
been selected on a drive.