Safety Integrated Functions
8.7 Commissioning
8.7.3.4

F-DI/F-DO configuration

Inputs screen F-DI
Figure 8-17
NC/NC contact (p10040)
Terminal property F-DI 0-2 (p10040.0 = F-DI 0, ... p10040.2 = F-DI 2): Configure only the
property of the second (lower) digital input. Always connect an NC contact to digital input 1
(upper). Digital input 2 can be configured as NO contact.
LED in F-DI screen
The LED downstream of the AND element indicates the logical state (inactive: gray, active:
green, discrepancy error: red).
348
Inputs screen
Function Manual, 10/2008, 6SL3097-4AB10-0BP0