Load Identification; Principle; Boundary Conditions - Parker Compax3 Operating Instructions Manual

Positioning via digital i/os & com port
Hide thumbs Also See for Compax3:
Table of Contents

Advertisement

Setting up Compax3
4.4.7.

Load identification

In this chapter you can read about:

Principle .........................................................................................................................244

Boundary conditions ......................................................................................................244

Process of the automatic determination of the load characteristic value (load identification)245
Tips ................................................................................................................................246
244
Automatic determination of the load characteristic value:
of the mass moment of inertia with rotary systems
of the mass with linear systems
4.4.7.1
Principle
The load characteristic value is automatically determined.
For this it is necessary to excite the system additionally with a signal (excitation
signal = noise).
The excitation signal is fed into the control loop. The control loop dampens the
excitation signal. Therefore, the superimposed control loop is set so slowly by
reducing the stiffness, that the measurement is not influenced.
A superimposed test movement is additionally possible. This helps to eliminate
possible mechanical effects such as rubbing caused by friction.
4.4.7.2
Boundary conditions
If the control is instable before the beginning of the measurement, please reduce
the stiffness (in the optimization window at the left bottom)
The following factors can disturb a measurement:
Systems with high friction (e.g. linear actuators with sliding guide)
Here, the systems where the static friction is considerably higher than the kinetic
friction (slip-stick effect) are especially problematic.
Systems with significant slack points (play)
Systems with "too light" or susceptible to oscillation bearing of the total drive
(rack).
Formation of rack resonances. (e.g. with gantries,...)
Non constant disturbance forces which influence the speed development. (e.g.
extremely strong slot moments)
The effects of the factors one to three on the measurement can be reduced by
using a test movement.
Caveat emptor (exclusion of warranty)
Due to multiple possibilities for disturbing influences of a real control path, we
cannot accept any liability for secondary damages caused by faultily determined
values. Therefore it is essential to verify all values automatically determined before
loading them into the control loop.