Mounting And Dimensions Psup/C3M; Mounting And Dimensions Psup10/C3M050D6, C3M100D6, C3M150D6 - Parker Compax3 Operating Instructions Manual

Positioning via digital i/os & com port
Hide thumbs Also See for Compax3:
Table of Contents

Advertisement

Compax3 device description
3.9.2.

Mounting and dimensions PSUP/C3M

Ventilation:
Information on
PSUP10D6/C3M050D6, C3M100D6, C3M150D6
72
During operation, the device radiates heat (power loss). Please provide for a
sufficient mounting distance below and above the device in order to ensure free
circulation of the cooling air. Please do also respect the recommended distances of
other devices. Make sure that the mounting plate is not exhibited to other
temperature influences than that of the devices mounted on this very plate. The
devices must be mounted vertically on a level surface. Make sure that all devices
are sufficiently fixed.
3.9.2.1
Mounting and dimensions PSUP10/C3M050D6,
C3M100D6, C3M150D6
The devices are force-ventilated via a ventilator fan fixed to the lower part of
Mounting spacing: At the top and below: at least 100mm
Mounting:
2 socket head screws M5
263mm
360mm
50mm
Tolerances: DIN ISO 2768-f
192-120113 N08 C3I12T11 - December 2010
the heat dissipator!
46mm
C3I12T11
50,5mm
90°
400mm