Compax3Sxxx V2; Main Voltage Supply C3S Connector X1 - Parker Compax3 Operating Instructions Manual

Positioning via digital i/os & com port
Hide thumbs Also See for Compax3:
Table of Contents

Advertisement

Parker EME
3.3.5.

Compax3Sxxx V2

In this chapter you can read about:

Main voltage supply C3S connector X1 ........................................................................... 35

Braking resistor / high voltage DC C3S connector X2 ..................................................... 36
Device protection
3.3.5.1
Main voltage supply C3S connector X1
By cyclically switching on and off the power voltage, the input current
limitation can be overloaded, which will cause a device error.
Therefore please wait at least 2 minutes after switching off before you switch
Power supply plug X1 for 1 AC 230VAC/240VAC devices
PIN
Designation
1
L
2
N
3
PE
Mains connection Compax3S0xxV2 1AC
Controller type
Supply voltage
Input current
Maximum fuse rating per device
(=short circuit rating)
* for UL conform operation (see on page 22), a miniature circuit breaker, K
characteristic, Type S203 is to be used.
Caution - Risk of Electric Shock!
Always switch devices off before wiring them!
Dangerous voltages are still present until 10 min. after switching off the power
supply.
Power supply plug X1 for 3AC 230VAC/240VAC devices
PIN
Designation
1
L1
2
L2
3
L3
4
PE
192-120113 N08 C3I12T11 - December 2010
the device on again!
S025V2
Single phase 230VAC/240VAC
80-253VAC / 50-60Hz
6Arms
10 A (MCB miniature
circuit breaker, K
characteristic)
Compax3 device description
S063V2
13Arms
16A (automatic circuit
breaker K)
35