Compax3Sxxx V4; Power Supply Connector X1 For 3Ac 400Vac/480Vac-C3S Devices - Parker Compax3 Operating Instructions Manual

Positioning via digital i/os & com port
Hide thumbs Also See for Compax3:
Table of Contents

Advertisement

Compax3 device description
3.3.6.

Compax3Sxxx V4

In this chapter you can read about:

Power supply connector X1 for 3AC 400VAC/480VAC-C3S devices ............................... 38

Braking resistor / high voltage supply connector X2 for 3AC 400VAC/480VAC_C3S devices
Connection of the power voltage of 2 C3S 3AC devices .................................................. 39
Device protection
Caution!
38
3.3.6.1
Power supply connector X1 for 3AC 400VAC/480VAC-
C3S devices
By cyclically switching on and off the power voltage, the input current
limitation can be overloaded, which will cause a device error.
Therefore please wait at least 2 minutes after switching off before you switch
PIN
Designation
1
L1
2
L2
3
L3
4
PE
Mains connection Compax3SxxxV4 3AC
Controller type
Supply voltage
Input current
Maximum fuse rating per
device(=short circuit
rating)
* for UL conform operation (see on page 22), a miniature circuit breaker, K
characteristic, Type S203 is to be used.
The 3AC V4 devices must only be operated with three phases!
Caution - Risk of Electric Shock!
Always switch devices off before wiring them!
Dangerous voltages are still present until 10 min. after switching off the power
supply.
192-120113 N08 C3I12T11 - December 2010
the device on again!
S015V4
S038V4
Three phase 3*400VAC/480VAC
80-528VAC / 50-60Hz
3Aeff
6Arms
6A
10A
MCB miniature circuit breaker, K characteristic
S075V4
S150V4
S300V4
10Arms
16Arms
22Arms
16A
20A
25A
C3I12T11
39