Labels for the Ethernet cable that connects the HUB and the agent
•
The label on the agent end should contain the serial number of the Ethernet port. The definitions
of the cabinet number and frame number are the same as those described in
If it is a stand-alone HUB without any cabinet or frame, the label should contain specific location
information that identifies the HUB.
The serial number on the HUB, the network port number of the agent and the location of
stand-alone server should be specified according to actual connection.
Example of the label
Figure 87 Example of the label on the Ethernet cable
"A01-03- 1 0-05" indicates that the local end of the Ethernet cable is connected with Ethernet Port 05, Slot
10, Frame 03 of the cabinet on Row A, Column 01 in the equipment room.
"B02-03- 1 2" indicates that the opposite end of the Ethernet cable is connected with Ethernet Port 12,
Frame 03 of the cabinet on Row B, Column 02 in the equipment room.
Engineering labels for optical fibers
These labels are affixed to the optical fibers that connect the optical interfaces on the boards in a frame,
or on the device boxes. There are two types of labels for optical fibers: one is for the fiber that connects
the optical interfaces on two devices, the other is for the fiber that connects the device and the Optical
Distribution Frame (ODF).
Labels for the fiber that connects two devices
Meaning of the label
Table 69
shows the information on both sides of the labels affixed to the optical fiber that connects two
devices.
Table 69 Information on labels affixed to the fiber between two devices
Content
MN-B-C-D-R/T
Meaning
MN: Cabinet number
147
Example
For example, A01
Table 68
above.