Power supply system failure

Power monitoring module
Table 27 Description of the LEDs on the power monitoring module
LED
RUN
MAJOR
MINOR
To troubleshoot the failures when the RUN LED of the power monitoring module is off:
Unplug and then plug the power monitoring module.
1.
If the RUN LED is still off, replace the power monitoring module.
2.
If the RUN LED is still off, contact H3C Technical Support for help.
3.
Power modules
Figure 53 LEDs on an AC power module
(1) Input status LED
Color
Status
On
Green
Off
On
Red
Flashing
Off
Yellow
Off
(2) Output status LED
Description
The power monitoring module is working properly.
The power monitoring module is faulty.
At least one power module is faulty.
All power modules have been removed from the power
frame.
The switch of the power frame is off.
Power modules are in position, but no AC power supply
is provided.
A power module is being inserted or removed.
The power modules are working properly.
Reserved
(3) Over-temperature alarm LED