13. Before Contacting your Toshiba distributor
- Trip information and remedies
13.1 Trip causes/warnings and remedies
When a problem arises, diagnose it in accordance with the following table.
If it is found that replacement of parts is required or the problem cannot be solved by any remedy described in the
table, contact your Toshiba distributor.
[Trip information]
Error code
Failure code
0001
0002
0003
0004
0005
*
0008
*
0009
000A
* You can select a trip ON/OFF by parameters.
Name
Overcurrent during
The acceleration time is too short.
acceleration
The V/F setting is improper.
A restart signal is input to the rotating
motor after a momentary stop, etc.
A special motor (e.g. motor with a small
impedance) is used.
The cable length to a motor is long.
Overcurrent during
The deceleration time is too short.
deceleration
The cable length to a motor is long.
Overcurrent during
The load fluctuates abruptly.
constant speed
The load is in an abnormal condition.
operation
The cable length to a motor is long.
Overcurrent (An
The insulation of the output main circuit or
overcurrent on the
motor is defective.
load side at start-up)
The motor has too small impedance.
Arm overcurrent at
A main circuit elements is defective.
start-up
Input phase failure
A phase failure occured in the input line of
the main circuit.
The capacitor in the main circuit lacks
capacitance.
Output phase failure
A phase failure occurred in the output line
of the main circuit.
The motor has too big impedance.
Overvoltage during
The input voltage fluctuates abnormally.
acceleration
(1) The power supply has a capacity of
200kVA or more.
(2) A power factor improvement capacitor is
opened or closed.
(3) A system using a thyristor is connected
to the same power distribution line.
A restart signal is input to the rotating
motor after a momentary stop, etc.
Description
Increase the acceleration time .
Check the V/F parameter.
Use (auto-restart) and
In case of pt=0, 1, decrease vb.
In case of pt=2, 3, 4, set f415
AC reactors etc. are required for the
Increase the deceleration time .
AC reactors etc. are required for the
Reduce the load fluctuation.
Check the load (operated machine).
AC reactors etc. are required for the
Check the secondary wiring and insulation
Set f613=2, 3
Contact your Toshiba distributor.
Check the main circuit input line for phase
Set input phase failure detection selection
Check the capacitor in the main circuit for
Check the main circuit output line, motor,
Set output phase failure detection
Insert a suitable input reactor.
Use (auto-restart) and
M-1
E6581595
Remedies
(ride-through control).
(Motor rated current) and make an auto-
tuning.
output side. (Refer to section 1.4.3-(4))
output side. (Refer to section 1.4.3-(4))
output side. (Refer to section 1.4.3-(4))
state.
failure.
f608=0.
exhaustion.
etc. for phase failure.
selection f605=0.
(ride-through control).
13