Chapter 7: Alerts, Automated Response and Logging
Note: Before configuring Environmental Checks as the trigger in Auto-Response you will need first to configure the Temp and/
or Humidity sensors on your attached EMD
7.1.2

Alarms and Digital Inputs

To set the status of any attached Smoke or Water sensors or digital inputs as the trigger event:
• Click on Alarms/ Digital Inputs as the Check Condition
• In the Alarms/ Digital Inputs Check menu, select the specific Alarm/Digital IO Pin that will trigger the Auto-Response
• Select Trigger on Change to trigger when alarm signal changes, or select to trigger when the alarm signal state changes to
either a Trigger Value of Open (0) or Closed (1)
• Check Save Auto-Response
Note: Before configuring Alarms/ Digital Inputs checks in Auto-Response you first must configure the sensor/DIO that is to be
attached to your EMD or ACM5000
7.1.3

UPS / Power Supply

To use the properties of any attached UPS as the trigger event:
• Click on UPS / Power Supply as the Check Condition
• Select UPS Power Device Property (Input Voltage, Battery Charge %, Load %, Input Frequency Hz or Temperature in °C)
that will checked for the trigger
• Specify the Trigger value that the check measurement must exceed or drop below to trigger the Auto-Response
• Select Comparison type as being Above Trigger Value or Below Trigger Value to trigger
• Specify any Hysteresis factor that is to be applied to environmental measurements (e.g. if an Auto-Response was set up
with a trigger event of a battery charge below 20% with a Hysteresis of 5 then the trigger condition would not be seen as
having been resolved till the battery charge was above 25%)
• Check Save Auto-Response
Note: Before configuring UPS checks in Auto-Response you first must configure the attached UPS
7.1.4

UPS Status

To use the alert state of any attached UPS as the Auto-Response trigger event:
• Click on UPS Status as the Check Condition
• Select the reported UPS State to trigger the Auto-Response (either On Battery or Low Battery). The Auto-Response will
resolve when the UPS state returns to the "Online" state
• Select which connected UPS Device to monitor and check Save Auto-Response
Note: Before configuring UPS state checks in Auto-Response you first must configure the attached UPS
114