Chapter 7: Alerts, Automated Response and Logging
• Check Disable Auto-Response at specific times and you will be able to periodically disable Auto-Responses between
specified times of day
To configure the condition that will trigger the Auto-Response:
• Click on the Check Condition type (e.g. Environmental, UPS Status or ICMP ping) to be configured as the trigger for this
new Auto-Response in the Auto-Response Settings menu
7.1.1
Environmental Check
To configure Humidity or Temperature levels as the trigger event:
• Click on the Environmental as the Check Condition
• In the Environmental Check menu, select the specific Environmental Sensor to be checked for the trigger
• Specify the Trigger value (in °C / °F for Temp and % for Humidity) that the check measurement must exceed or drop below
to trigger the AutoResponse
• Select Comparison type as being Above Trigger Value or Below Trigger Value to trigger
• Specify any Hysteresis factor that is to be applied to environmental measurements (e.g. if an Auto-Response was set up
with a trigger event of a temp reading above 49°C with a Hysteresis of 4 then the trigger condition would not be seen as
having been resolved till the temp reading was below 45°C)
• Check Save Auto-Response
113