2.1.5: Utility Peak Demand

The Shark® 100 meter provides user-configured Block (Fixed) Window or Rolling Window
Demand. This feature allows you to set up a Customized Demand Profile. Block Window Demand
is demand used over a user-configured demand period (usually 5, 15 or 30 minutes). Rolling
Window Demand is a fixed window demand that moves for a user-specified subinterval period. For
example, a 15-minute Demand using 3 subintervals and providing a new demand reading every 5
minutes, based on the last 15 minutes.
Utility Demand Features can be used to calculate kW, kVAR, kVA and PF readings. All other
parameters offer Max and Min capability over the user-selectable averaging period. Voltage
provides an Instantaneous Max and Min reading which displays the highest surge and lowest sag
seen by the meter

2.2: Specifications

Power Supply
Range:
Power Consumption:
Voltage Inputs (Measurement Category III)
Range:
Supported hookups:
Input Impedance:
Burden:
Pickup Voltage:
Connection:
Max Input Wire Gauge:
Fault Withstand:
Reading:
Current Inputs
Class 10:
Class 2:
Burden:
Pickup Current:
Connections:
Fault Withstand:
Reading:
e
Electro Industries/GaugeTech
D2 Option: Universal, (90 to 265) VAC @50/60Hz or (100 to
370) VDC
D Option: (18-60) VDC
5 VA, 3.5W
Universal, Auto-ranging up to 416Vac L-N, 721Vac L-L
3 Element Wye, 2.5 Element Wye, 2 Element Delta, 4 Wire
Delta
1M Ohm/Phase
0.0144VA/Phase at 120 Volts
10Vac
Screw terminal (Diagram 4.4)
AWG#12 / 2.5mm2
Meets IEEE C37.90.1
Programmable Full Scale to any PT Ratio
5A Nominal, 10A Maximum
1A Nominal, 2A Maximum
0.005VA Per Phase Max at 11 Amps
0.1% of Nominal
O or U Lug Electrical Connection (Diagram 4.1)
Pass-through Wire, 0.177" / 4.5mm Maximum Diameter
(Diagram 4.2)
Quick Connect, 0.25" Male Tab (Diagram 4.3)
100A/10sec., 300A/3sec., 500A/1sec.
Programmable Full Scale to any CT Ratio
Doc #: E145701