Electro Industries Shark 100 Installation & Operation Manual page 90

Low cost, high performance multifunction electricity meter
Hide thumbs Also See for Shark 100:
Table of Contents

Advertisement

Modbus Address
Hex
Decimal
7536 - 7536 30007 - 30007 Operating Mode Screen Enables
7537 - 753D 30008 - 30014 Reserved
753E - 753E 30015 - 30015 User Settings Flags
753F - 753F 30016 - 30016 Full Scale Current (for load % bargraph)
7540 - 7547 30017 - 30024 Meter Designation
7548 - 7548 30025 - 30025 COM1 setup
7549 - 7549 30026 - 30026 COM2 setup
754A - 754A 30027 - 30027 COM2 address
754B - 754B 30028 - 30028 Limit #1 Identifier
754C - 754C 30029 - 30029 Limit #1 Out High Setpoint
754D - 754D 30030 - 30030 Limit #1 In High Threshold
754E - 754E 30031 - 30031 Limit #1 Out Low Setpoint
754F - 754F 30032 - 30032 Limit #1 In Low Threshold
7550 - 7554 30033 - 30037 Limit #2
7555 - 7559 30038 - 30042 Limit #3
755A - 755E 30043 - 30047 Limit #4
755F - 7563 30048 - 30052 Limit #5
7564 - 7568 30053 - 30057 Limit #6
e
Electro Industries/GaugeTech
1
Description
Format
UINT16
UINT16
UINT16
ASCII
UINT16
UINT16
UINT16
UINT16
SINT16
SINT16
SINT16
SINT16
SINT16
SINT16
SINT16
SINT16
SINT16
Doc# E145701
Units or
6
Range
Resolution
00000000 eeeeeeee
bit-mapped
bit-mapped
---g--nn srp--wf-
0 to 9999
none
16 char
none
----dddd -0100110
bit-mapped
----dddd -ppp-bbb
bit-mapped
1 to 247
none
0 to 65535
-200.0 to +200.0
0.1% of full scale
-200.0 to +200.0
0.1% of full scale
-200.0 to +200.0
0.1% of full scale
-200.0 to +200.0
0.1% of full scale
same as Limit #1
same as Limit #1
Comments
eeeeeeee = op mode screen rows on(1) or
off(0), rows top to bottom are bits low order
to high order
g = enable alternate full scale bargraph
current (1=on, 0=off)
nn = number of phases for voltage &
current screens (3=ABC, 2=AB, 1=A,
0=ABC)
s = scroll (1=on, 0=off)
r = password for reset in use (1=on, 0=off)
p = password for configuration in use
(1=on, 0=off)
w = pwr dir (0-view as load, 1-view as
generator)
f = flip power factor sign (1=yes, 0=no)
If non-zero and user settings bit g is set,
this value replaces CT numerator in the full
scale current calculation.
dddd = reply delay (* 50 msec)
ppp = protocol (1-Modbus RTU, 2-Modbus
ASCII, 3-DNP)
bbb = baud rate (1-9600, 2-19200, 4-
38400, 6-57600)
use Modbus address as the identifier (see
notes 7, 11, 12)
Setpoint for the "above" limit (LM1), see
notes 11-12.
Threshold at which "above" limit clears;
normally less than or equal to the "above"
setpoint; see notes 11-12.
Setpoint for the "below" limit (LM2), see
notes 11-12.
Threshold at which "below" limit clears;
normally greater than or equal to the "below
setpoint; see notes 11-12.
same as Limit #1
MM-6
#
Reg
1
7
1
1
8
1
1
1
1
1
1
1
1
5
5
5
5
5