Electro Industries Shark 100 Installation & Operation Manual page 29

Low cost, high performance multifunction electricity meter
Hide thumbs Also See for Shark 100:
Table of Contents

Advertisement

Isolation
All Inputs and Outputs are galvanically isolated to 2500 Vac
Environmental Rating
Storage:
Operating:
Humidity:
Faceplate Rating:
Measurement Methods
Voltage, Current:
Power:
A/D Conversion:
Update Rate
Watts, VAR and VA:
All other parameters:
Communication Format
1. RS-485 Port through Back Plate
2. IrDA Port through Face Plate
3. RS-485P - RS-485 and KYZ Pulse
Protocols:
Com Port Baud Rate:
Com Port Address:
Data Format:
Shark 100T
Mechanical Parameters
Dimensions:
Weight:
e
Electro Industries/GaugeTech
0
(-40 to +85)
C
0
(-30 to +70)
C
to 95% RH Non-condensing
NEMA12 (Water Resistant), Mounting Gasket Included
True RMS
Sampling at 400+ Samples per Cycle on All Channels Measured
Readings Simultaneously
6 Simultaneous 24 bit Analog to Digital Converters
100 milliseconds (Ten times per second)
1 second
Modbus RTU, Modbus ASCII, DNP 3.0 (V3 and V4
V-Switches)
9600 to 57,600 b/s
001-247
8 Bit, No Parity
Default Initial Communication Baud 9600 (see Chapter 5)
(H4.85 x W4.82 x L4.25) inches, (H123.2 x W123.2 x
L105.4) mm
Mounts in 92mm square DIN or ANSI C39.1, 4" Round Cut-out
2 pounds, 0.907kg (ships in a 6"/152.4mm cube container)
Doc #: E145701
2-5

Advertisement

Table of Contents
loading

This manual is also suitable for:

Shark 100tShark 100

Table of Contents