Object Point Var
Description
Binary Output States
10
0
2 Reset Energy Counters
10
1
2 Change to Modbus RTU
Protocol
Control Relay Outputs
12
0
1 Reset Energy Counters
12
1
1 Change to Modbus RTU
Protocol
Binary Counters (Primary)
20
0
4 W-hours, Positive
20
1
4 W-hours, Negative
20
2
4 VAR-hours, Positive
20
3
4 VAR-hours, Negative
20
4
4 VA-hours, Total
Analog Inputs (Secondary)
30
0
5 Meter Health
30
1
5 Volts A-N
30
2
5 Volts B-N
30
3
5 Volts C-N
30
4
5 Volts A-B
30
5
5 Volts B-C
30
6
5 Volts C-A
30
7
5 Amps A
30
8
5 Amps B
30
9
5 Amps C
e
Electro Industries/GaugeTech
Format
Range
BYTE
Always 1
BYTE
Always 1
N/A
N/A
N/A
N/A
UINT32
0 to 99999999
UINT32
0 to 99999999
UINT32
0 to 99999999
UINT32
0 to 99999999
UINT32
0 to 99999999
SINT16
0 or 1
SINT16
0 to 32767
SINT16
0 to 32767
SINT16
0 to 32767
SINT16
0 to 32767
SINT16
0 to 32767
SINT16
0 to 32767
SINT16
0 to 32767
SINT16
0 to 32767
SINT16
0 to 32767
Doc # E145701
Multiplier
Units
Comments
N/A
none
N/A
none
Responds to Function 5 (Direct Operate),
Qualifier Code 17x or 28x, Control Code 3,
N/A
none
Count 0, On 0 msec, Off 1 msec ONLY.
Responds to Function 6 (Direct Operate -
No Ack), Qualifier Code 17x, Control Code
N/A
none
3, Count 0, On 0 msec, Off 1 msec ONLY.
(n-d)
W hr
example:
multiplier = 10
,
where n and d are
energy format = 7.2K and W-hours counter
W hr
derived from the
= 1234567
energy format. n = 0,
VAR hr
n=3 (K scale), d=2 ( 2 digits after decimal
3, or 6 per energy
VAR hr
point), multiplier = 10
format scale and d =
energy is 1234567 * 10 Whrs, or 12345.67
number of decimal
VA hr
KWhrs
places.
N/A
none
0 = OK
(150 / 32768)
V
(150 / 32768)
Values above 150V secondary read 32767.
V
(150 / 32768)
V
(300 / 32768)
V
(300 / 32768)
Values above 300V secondary read 32767.
V
(300 / 32768)
V
(10 / 32768)
A
Values above 10A secondary read 32767.
(10 / 32768)
A
(10 / 32768)
A
Read via Class 0 only
Read via Class 0 only
(3-2)
1
= 10
= 10, so
Read via Class 0 only
DNP-1