Settings
Password
(Meter is shipped with Password Disabled and
there is NO DEFAULT PASSWORD)
Enable Password for Reset
Enable Password for Configuration
Change Password
Change VSwitch
(Call Electro Industries for Update Information)
Change Device Designation
Limits (VSwitch 4 Only)
For up to 8 Limits, Set:
Address: Modbus Address (1 based)
Label: Your Designation
High Set Point: % of Full Scale
Example:
100% of 120VFS = 120V
90% of 120V FS = 108V
Return Hysteresis: Point to go back in Limit
Example:
High Set Point
(Out of Limit at 132V)
Return Hysteresis = 105%
(Stay Out until 126V)
Low Set Point: % of Full Scale
Return Hysteresis: Point to go back in Limit
Settings appear in the Table at the bottom
of the screen
NOTE: If Return Hysteresis is > High Set Point,
the Limit is Disabled.
Click Update to send a new Profile.
NOTE: If the Update fails, the software asks if you want to try again to Update.
Click Cancel to Exit the Profile.
Use Communicator EXT to communicate with the device and perform required tasks.
Refer to the Communicator EXT User's Manual for more details.