Electro Industries Shark 100 Installation & Operation Manual page 88

Low cost, high performance multifunction electricity meter
Hide thumbs Also See for Shark 100:
Table of Contents

Advertisement

Modbus Address
Hex
Decimal
0FAF - 0FAF
4016 - 4016 Phase A Voltage 2nd harmonic magnitude
0FB0 - 0FB0
4017 - 4017 Phase A Voltage 3rd harmonic magnitude
0FB1 - 0FB8
4018 - 4025 Phase B Current harmonic magnitudes
0FB9 - 0FBC
4026 - 4029 Phase B Voltage harmonic magnitude
0FBD - 0FC4
4030 - 4037 Phase C Current harmonic magnitudes
0FC5 - 0FC8
4038 - 4041 Phase C Voltage harmonic magnitude
14
Phase Angle Block
1003 - 1003
4100 - 4100 Phase A Current
1004 - 1004
4101 - 4101 Phase B Current
1005 - 1005
4102 - 4102 Phase C Current
1006 - 1006
4103 - 4103 Angle, Volts A-B
1007 - 1007
4104 - 4104 Angle, Volts B-C
1008 - 1008
4105 - 4105 Angle, Volts C-A
Status Block
1387 - 1387
5000 - 5000 Meter Status
1388 - 1388
5001 - 5001
Limits Status
1389 - 138A
5002 - 5003 Time Since Reset
9
Resets Block
4E1F - 4E1F 20000 - 20000 Reset Max/Min Blocks
4E20 - 4E20 20001 - 20001 Reset Energy Accumulators
Meter Programming Block
55EF - 55EF 22000 - 22000 Initiate Programmable Settings Update
55F0 - 55F0 22001 - 22001 Terminate Programmable Settings Update
55F1 - 55F1 22002 - 22002 Calculate Programmable Settings Checksum
e
Electro Industries/GaugeTech
1
Description
7
Commands Section
3
3
6
Format
Range
UINT16
0 to 65535
none
UINT16
0 to 65535
none
same as Phase A Current 0th to 7th harmonic magnitudes
same as Phase A Voltage 0th to 3rd harmonic magnitudes
same as Phase A Current 0th to 7th harmonic magnitudes
same as Phase A Voltage 0th to 3rd harmonic magnitudes
SINT16
-1800 to +1800
0.1 degree
SINT16
-1800 to +1800
0.1 degree
SINT16
-1800 to +1800
0.1 degree
SINT16
-1800 to +1800
0.1 degree
SINT16
-1800 to +1800
0.1 degree
SINT16
-1800 to +1800
0.1 degree
--exnpch ssssssss
UINT16
bit-mapped
87654321 87654321
UINT16
bit-mapped
UINT32
0 to 4294967294
4 msec
4
5
UINT16
password
5
UINT16
password
5
UINT16
password
UINT16
any value
UINT16
Doc# E145701
Units or
Resolution
Comments
exnpch = EEPROM block OK flags
(e=energy, x=max, n=min, p=programmable
settings, c=calibration, h=header),
ssssssss = state (1=Run, 2=Limp, 10=Prog
Set Update via buttons, 11=Prog Set
Update via IrDA, 12=Prog Set Update via
COM2)
high byte is setpt 1, 0=in, 1=out
low byte is setpt 2, 0=in, 1=out
wraps around after max coun
meter enters PS update mode
meter leaves PS update mode via reset
meter calculates checksum on RAM copy
of PS block
#
Reg
1
1
8
4
8
4
Block Size:
42
read-only
1
1
1
1
1
1
Block Size:
6
read-only
1
1
2
Block Size:
4
write-only
1
1
Block Size:
2
read/conditional write
1
1
1
MM-4

Advertisement

Table of Contents
loading

This manual is also suitable for:

Shark 100tShark 100

Table of Contents