7.3.3: Configuration Mode
The next Mode on the Main Menu is Configuration Mode. See Appendix A for Navigation Map.
To reach Configuration Mode, push the MENU Button from any of the Auto-Scrolling Readings,
then push the DOWN button to reach the String for Configuration Mode (CFG).
Push ENTER and the Configuration Parameters scroll, starting at the "SCROLL, Ct, Pt" screen.
Push the DOWN Button to scroll all the parameters: Scroll, CT, PT, Connection (Cnct) and Port.
The 'Active" parameter is in the A Screen and is flashing.
7.3.3.1: Configure Scroll Feature
Push ENTER and the Scroll no screen appears.
Push RIGHT and changes to Scroll YES.
When in Scroll Mode, the unit scrolls each parameter for 7 seconds on and 1 second off. The meter
can be configured through software to display only selected screens. If that is the case, it will only
scroll the selected display. Additionally, the meter will only scroll the display enabled by the
V-Switch that is installed.
Push ENTER (YES or no) and the screen scrolls to the Ct Parameters.
e
Electro Industries/GaugeTech
Doc # E145701
7-4