Signaling Contact - Siemens SCALANCE X-200 Operating Instructions Manual

Industrial ethernet switches
Hide thumbs Also See for SCALANCE X-200:
Table of Contents

Advertisement

Connection

5.2 Signaling contact

5.2
Signaling contact
Signaling contact
The signaling contact (relay contact) is a floating switch with which error/fault states can be
signaled by breaking the contact.
The signaling contact is connected to a 2-pin plug-in terminal block.
Exception:
The signaling contact on the SCALANCE X204 IRT PRO and SCALANCE X202-2P IRT
PRO is connected using a 5-pin b-coded M12 socket.
IE Switches X-200
Pin number
Pin 1
Pin 2
-
-
-
The following errors/faults can be signaled by the signaling contact:
● The loss and the establishment of a link on a monitored port.
● The failure of one of the two redundant power supplies.
● The loss of the connection to the controller in PROFINET IO mode.
● The redundancy manager signals an error
Note
SCALANCE X204 IRT PRO, SCALANCE X202-2P IRT PRO and SCALANCE X201-3P
IRT PRO have no redundant power supply
● Incompatible C-PLUG was inserted.
The connection or disconnection of a communication node on an unmonitored port does not
lead to an error message.
140
SCALANCE X204 IRT PRO,
SCALANCE X202-2P IRT PRO,
SCALANCE X201-3P IRT PRO
Assignment
Pin number
F1
Pin 1
F2
Pin 2
-
Pin 3
-
Pin 4
-
Pin 5
Operating Instructions, 12/2011, A5E00349864-19
Assignment
F1
n. c.
n. c.
F2
n. c.
SCALANCE X-200

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents