Contact
L1+
M1
M2
L2+
5.4

Signaling contact

Information on the signaling contact
● The signaling contact is a floating switch that signals error statuses by opening the contact.
The signaling contact must be operated within the range of the operating voltage.
If an error/fault occurs, the signaling contact opens. In normal operation, the signaling
contact is closed.
● The signaling contact is connected using a 2-pin plug-in terminal block (spring-loaded
terminal). The terminal block ships with the device and can also be ordered as a spare part.
● Note the wiring rules.
NOTICE
Damage due to voltage being too high
The signaling contact can be subjected to a maximum load of 100 mA (safety extra‑low
voltage SELV, 24 VDC).
Higher voltages or currents can damage the device.
Position and assignment
Figure 5-2
SCALANCE XC-200
Operating Instructions, 12/2017, C79000-G8976-C442-03
Position of the signaling contact based, for example on the SCALANCE XC-200 with 8
ports and assignment of the terminal block
Assignment
24 VDC
Ground
Ground
24 VDC
Connecting up
5.4 Signaling contact
53