Problem
HW Event
Description
Category
The disk
none
enclosure does
not power on
System fault LED
none
is on
Critical
Buzzer sounds
Critical
when BCC
installed
BCC Fault LED is
Critical
on
Fan LED is
Critical
amber
598
LED State
Status
System
none
Power LED
off
Power
Power
Supply LED
supply Not
off
Available
Part Fault
Critical
LED on
BCC Fault
Critical
flashing
BCC Fault
Critical
on
Amber
Critical
Probable Cause/Solution
– Neither power cord is plugged in.
– The power switch is not pressed.
– AC breaker is tripped.
– AC power source has failed.
– The PDU/PDRU is defective.
– Power switch is defective.
– A faulty component is causing
power supplies to turn off.
Remove all components and
reinsert one at a time until the
faulty component is isolated.
– The power supply is not plugged
in.
– The PDU/PDRU or primary power
source has failed.
A component has failed. See
problem descriptions below.
BCC DIP switch settings do not
match peer BCC switch settings.
Reset switches.
BCC hardware is faulty. Replace the
BCC.
Fan has slowed or stopped. Replace
the fan.