Output:voltage:amplitude; Output:voltage:amplitude <Amplitude>,(@<Ch_List>); Output:voltage:amplitude? (@<Channel>) - VXI VT1422A User Manual

Remote channel multi-function dac module user’s and scpi programming manual
Table of Contents

Advertisement

OUTPut

OUTPut:VOLTage:AMPLitude

Note
Parameters
Comments
Usage
OUTPut:VOLTage:AMPLitude?
Comments
Usage
322 VT1422A Command Reference
OUTPut:VOLTage:AMPLitude <amplitude>,(@<ch_list>)
voltage on programmable Strain Bridge Completion SCPs pointed to by <ch_list>
(the VT1511A for example).
This command is not used to set output voltage on SCPs like the VT1531A Voltage
Output SCP.
Parameter
Parameter
Name
Type
amplitude
numeric (float32)
ch_list
channel list (string)
To turn off excitation voltage (when using external voltage source) program
<amplitude> to 0.
Related Commands: OUTP:VOLT:AMPL?
*RST Condition: MIN (0) for VT1511A
Send with VXIplug&play Function: hpe1422_cmd(...)
OUTP:VOLT:AMPL 5,(@116:119)
OUTPut:VOLTage:AMPLitude? (@<channel>)
excitation voltage for the channel specified by <channel>. If the channel is not on a
VT1511A SCP, the query will return zero.
The <channel> parameter must specify a single channel only.
Returned Value: Numeric, one of 0, 1, 2, 5, or 10 for VT1511A SCP, 3.9 for
non- programmable VT1506A/07A SCPs. Data type is float32.
Related Commands: OUTP:VOLT:AMPL
Send with VXIplug&play Function: hpe1422_cmdReal64_Q(...)
OUTP:VOLT:AMPL? (@103)
sets the excitation
Range of
Values
MIN | 0 |1 | 2 | 5 | 10 | MAX
100 - 163
set excitation voltage for channels 16
through 19
returns the current setting of
returns current setting of excitation
voltage for channel 3
Default
Units
none
none
Chapter 7