Cisco 6503 - Catalyst Firewall Security Sys Installation Manual page 248

Installation guide
Hide thumbs Also See for 6503 - Catalyst Firewall Security Sys:
Table of Contents

Advertisement

Removing and Installing the DC-Input Power Supplies
Installing the 4000 W Power Supply (Wiring for 2700 W Operation; Left Power Bay)
Refer to
You should allow a minimum of 2.5 to 3 inches (63.5 mm to 76.2 mm) of space between the side of the
Note
power supply and any obstructions (such as the side of an enclosed equipment rack). This space is needed
to install and secure the DC-input power cables correctly. Incorrectly routing the DC-input power cables
can cause airflow blockage into the power supply and inadequate strain relief in the cables. The exact
amount of space required depends upon the gauge and flexibility of the DC-input power cables that you
are using.
Note
For proper 2700 W redundant power configurations, source DC for one 4000 W DC-input power supply
must come from the same battery system (A feed); source DC for the other 4000 W DC-input power
supply must come from another battery system (B feed).
For multiple DC-input power supplies, each DC input must be protected by a dedicated circuit breaker
Note
or a fuse. The circuit breaker or fuse must be sized according to the power supply input rating and the
local or national electrical code requirements.
To install a 4000 W DC-input power supply and wire it for 2700 W operation in the left power bay
(POWER 1), follow these steps:
Ensure that the system (earth) ground connection has been made.
Step 1
For ground connection installation instructions, see the
page
Remove the power supply from its shipping container and remove any packaging.
Step 2
Verify that source DC power is off to the DC circuit that feeds the power supply that you are installing.
Step 3
As an added precaution, place the appropriate safety flag and lockout devices at the source power circuit
breaker, or place a piece of adhesive tape over the circuit breaker handle to prevent accidental power
restoration while you are working on the circuit.
Prepare the source DC power cables by attaching the appropriately sized lugs.
Step 4
The power supply terminal block lug opening width is 0.62 inch (15.8 mm). The terminal posts are
centered 0.63 inches (15.88 mm) apart and have a 1/4-20 thread. We recommend that you use an
appropriately sized industry standard 2-hole, standard barrel compression lug. (See
power supply ground posts, located below the terminal block, also have 1/4-20 threads and require two
1/4-inch split-ring washers and two 1/4-20 hex nuts.
The DC-input wires and the DC power supply ground wires should be sized according to the local and
national installation requirements. Use only copper wire. For North American installations, use
90°C-rated, fine-strand copper conductors.
Catalyst 6500 Series Switches Installation Guide
4-42
Figure 4-26
for item location and identification on the 4000 W DC-input power supply.
3-52.
Chapter 4
Removal and Replacement Procedures
"Establishing the System Ground" section on
Figure
4-29.) The
OL-5781-08

Advertisement

Table of Contents
loading

This manual is also suitable for:

Catalyst 6500 series

Table of Contents