Chapter 4
Removal and Replacement Procedures
To install a 4000 W DC-input power supply and wire it for 2700 W operation in the right power supply
bay (POWER 2), follow these steps:
Ensure that the system (earth) ground connection has been made.
Step 1
For ground connection installation instructions, see the
page
3-52.
Remove the power supply from its shipping container and remove any packaging.
Step 2
Verify that source DC is off to the DC circuit that feeds the power supply that you are installing. As an
Step 3
added precaution, place the appropriate safety flag and lockout devices at the source power circuit
breaker, or place a piece of adhesive tape over the circuit breaker handle to prevent accidental power
restoration while you are working on the circuit.
Step 4
Prepare the source DC power cables by attaching the appropriately sized lugs.
The power supply terminal block lug opening width is 0.62 inch (15.8 mm). The terminal posts are
centered 0.63 inches (15.88 mm) apart and have a 1/4-20 thread. We recommend that you use an
appropriately sized industry standard 2-hole, standard barrel compression lug. (See
power supply ground posts, located below the terminal block, also have 1/4-20 threads and require two
1/4-inch split-ring washers and two 1/4-20 hex nuts.
The DC-input wires and the DC power supply ground wires should be sized according to the local and
national installation requirements. Use only copper wire. For North American installations, use
90°C-rated, fine-strand copper conductors.
Figure 4-32
Ø .267
2 holes
All measurements in inches
Use both hands to install and remove power supplies. Each DC-input power supply weighs 32 pounds
Caution
(14.5 kg).
Grasp the power supply handle with one hand, and place your other hand underneath the power supply.
Step 5
Slide the supply into the right-side power supply bay. Make sure that the power supply is fully seated in
the bay. (See
OL-5781-08
DC Power Cable Lug
2.25
Crimp area
.25
.63
.37
Figure
4-33.)
Removing and Installing the DC-Input Power Supplies
"Establishing the System Ground" section on
Catalyst 6500 Series Switches Installation Guide
Figure
4-32.) The
4-47