Chapter 4
Removal and Replacement Procedures
Removing a 2700 W AC-Input Power Supply
To remove a 2700 W AC-input power supply, follow these steps:
Turn the power switch to the off (0) position on the power supply you are removing.
Step 1
Disconnect the power cord from the power source. Do not touch the metal prongs on the power cord
Step 2
while it is still connected to the power supply.
Step 3
Remove the power cord from the power connection on the power supply.
Loosen the captive installation screws on the power supply. (See
Step 4
Figure 4-4
3
1
2
3
Step 5
Grasp both power supply handles, as shown in
the chassis.
OL-5781-08
2700 W AC-Input Power Supply Captive Installation Screws
1
P W R - 2
7 0 0 - A C
5
Power on/off switch
Power supply fan
Captive installation screw
Removing and Installing the AC-Input Power Supplies
/ 4
4
4
Status LEDs
5
AC In receptacle
Figure
4-5, and slide the power supply completely out of
Catalyst 6500 Series Switches Installation Guide
Figure
4-4.)
2
3
4-7