Chapter 4
Removal and Replacement Procedures
Removing the Fan Tray
The fan Tray is designed to be removed and replaced while the system is operating without presenting
an electrical hazard or damage to the system.
Warning
When removing the fan tray, keep your hands and fingers away from the spinning fan blades. Let the
fan blades completely stop before you remove the fan tray. Statement 258
To remove the existing fan assembly, follow these steps:
If you are upgrading your chassis from a fan tray 1 (low speed) to a fan tray 2 (high speed) and your
Step 1
chassis is equipped with a Supervisor Engine 2, you need to check that the current chassis configuration
supports the fan tray upgrade. To do this, use the command hw-module fan-tray version 2 to check for
configuration problems, such as power supply compatibility and power sufficiency.
If the system does not detect any configuration issues, a message is displayed saying that it is OK to
change the fan trays. If your chassis has either a Supervisor Engine 32 or a Supervisor Engine 720, skip
this step and proceed to Step 2.
Locate the fan assembly in the chassis as follows:
Step 2
•
•
•
•
•
•
A fully loaded cable management system can be heavy. Make sure that you provide proper support when
Caution
lowering the cable guide.
•
•
Loosen the two fan tray captive installation screws by turning them counterclockwise.
Step 3
OL-5781-08
Catalyst 6503 and Catalyst 6503-E switches—The fan tray is located to the left of the module cage.
(See
Figure
4-64.)
Catalyst 6504-E switch—The fan tray is located to the left of the module cage. (See
Catalyst 6506 and Catalyst 6506-E switches—The fan tray is located to the left of the module cage.
(See
Figure
4-66.)
Catalyst 6509 and Catalyst 6509-E switches—The fan tray is located to the left of the module cage.
(See
Figure
4-67.)
Catalyst 6509-NEB switch—The fan tray is located above the module cage. (See
Catalyst 6509-NEB-A and Catalyst 6509-V-E switches —On those switch chassis equipped with the
optional cable management system, you must first loosen the two captive installation screws located
at the top of the cable management system and fold the cable guide down to access the fan assembly.
(See
Figure
4-69.) See
Figure 4-70
switch.
Make sure there is adequate slack in the network interface cables to allow the cable guide to
Note
pivot down far enough to access the fan tray. If there is insufficient slack in the cables, the
cable guide will not pivot far enough to give you access to the fan trays.
Catalyst 6513 switch—The fan tray is located to the left of the module cage. (See
Catalyst 6513-E switch—The fan tray is located to the left of the module cage. Access to the fan
tray is from the rear of the chassis. (See
for the location of the two fan trays on the Catalyst 6509-NEB-A
Figure
4-72.)
Catalyst 6500 Series Switches Installation Guide
Removing and Installing the Fan Tray
Figure
4-65.)
Figure
4-68.)
Figure
4-71.)
4-83