Modification Of Interface Parameters - Beko QWIK-PURE CS Installation And Operating Manual

Table of Contents

Advertisement

QWIK‑PURE
®
iCS

3.5.3.3 Modification of interface parameters

This procedure is used to change interface parameters required for communication.
1. Write the value 0xAC1D (decimal: 44061) to the holding register 0x1392 (decimal: 5010).
2. Write the parameter to the holding register 0x07D0 (decimal: 2000).
Description / explanation
HighByte:
See the following table
LowByte:
Modbus server address 1 ... 246
Example value:
0x070A (decimal: 1802)
Interface parameters see table Index 0x07 (decimal: 7)
Client address 0x0A (decimal: 10)
4. To save the settings, write the value 0xBA5E (decimal: 47710) to the holding register 0x139C
(decimal: 5020).
5. Switch the product off and on again. 
0 The changes take effect approx. 10 seconds after the restart.
Parameter
Baud
Selection
Rate
[Bd]
0x00
4800
0x01
4800
0x02
4800
0x03
9600
0x04
9600
0x05
9600
0x06
19200
0x07
19200
0x08
19200
0x09
38400
0x0A
38400
0x0B
38400
30 | 132
HighByte
Parity
Stop Bit
No
2
Even
1
Odd
1
No
2
Even
1
Odd
1
No
2
Even
1
Odd
1
No
2
Even
1
Odd
1
Parameter
Baud
Selection
Rate
[Bd]
0x0C
57600
0x0D
57600
0x0E
57600
0x0F
76800
0x10
76800
0x11
76800
0x12
115200
0x13
115200
0x14
115200
Installation and operating manual
HighByte
Parity
Stop Bit
No
2
Even
1
Odd
1
No
2
Even
1
Odd
1
No
2
Even
1
Odd
1

Advertisement

Table of Contents
loading