This parameter is active only when parameter 8-01 Control Site is set to [0] Digital and control word.
Select control of the drive start function via the terminals (digital input) and/or via the bus.
Table 195: Option:
[0]
Digital input
Activate a start command via a digital input.
[1]
Bus
Activate a start command via the serial communication port.
[2]
Logic AND
Activate a start command via the fieldbus/serial communication port, and via 1 of the digital inputs.
[3]
Logic OR
Activate a start command via the serial communication port or via 1 of the digital inputs.
8-54 Reversing Select
Default value: [0] Digital input
Conversion index: -
This parameter is active only when parameter 8-01 Control Site is set to [0] Digital and control word.
Select control of the drive reverse function via the terminals (digital input) and/or via the bus.
Table 196: Option:
[0]
Digital input
Activate a reverse command via a digital input.
[1]
Bus
Activate a reverse command via the serial communication port.
[2]
Logic AND
Activate a reverse command via the fieldbus/serial communication port, and via 1 of the digital inputs.
[3]
Logic OR
Activate a reverse command via the serial communication port or via 1 of the digital inputs.
8-55 Set-up Select
Default value: [3] Logic OR
Conversion index: -
This parameter is active only when parameter 8-01 Control Site is set to [0] Digital and control word.
Select control of the drive setup selection via the terminals (digital input) and/or via the bus.
Table 197: Option:
[0]
Digital input
Activate the setup selection via a digital input.
[1]
Bus
Activate the setup selection via the serial communication port.
[2]
Logic AND
Activate the setup selection via the fieldbus/serial communication port, and via 1 of the digital inputs.
[3]
Logic OR
Activate the setup selection via the serial communication port or via 1 of the digital inputs.
8-56 Preset Reference Select
Default value: [3] Logic OR
Conversion index: -
Danfoss A/S © 2022.05
N O T I C E
Parameter type: Option
Data type: u_int8
N O T I C E
Parameter type: Option
Data type: u_int8
N O T I C E
Parameter type: Option
Data type: u_int8
2-setup: All setups
Change during operation: True
2-setup: All setups
Change during operation: True
2-setup: All setups
Change during operation: True
AU370727746889en-000101 / 130R0994 | 105