VLT® HVAC Drive FC 131
Programming Guide
5.5.39 WARNING/ALARM 95, Broken Belt
Cause
Torque is below the torque level set for no load, indicating a broken belt. See parameter group 22-6* Broken Belt Detection.
Troubleshooting
Troubleshoot the system.
Reset the drive after the fault is cleared.
5.5.40 ALARM 99, Locked Rotor
Cause
The rotor is blocked.
For 18–30 kW: If the protection is triggered more than 10 repeated times, auto reset transitions to require a manual operation to
clear the alarm.
Troubleshooting
Ensure that the rotor can operate freely.
Check the settings in parameter group 1-1* Motor Selection.
Check the settings in parameter group 1-2* Motor Data.
5.5.41 ALARM 101, Flow/pressure Info Missing
Cause
Sensorless-pump table is missing or wrong.
Troubleshooting
Download sensorless-pump table again.
5.5.42 ALARM 126, Motor Rotating
Cause
High back-EMF voltage.
Troubleshooting
Stop the rotor of the PM motor.
5.5.43 WARNING 127, Back EMF Too High
Cause
This warning applies to PM motors only. When the back-EMF exceeds 90% x U
normal level within 5 s, this warning is reported. The warning remains until the back EMF returns to a normal level.
Troubleshooting
Check the settings in parameter group 1-2* Motor Data.
5.5.44 WARNING 159, Check Valve Failure
When the drive is not in operation, a broken check valve leads to the motor runs in reverse.
Troubleshooting
Troubleshoot the system.
Reset the drive when the fault is cleared.
5.5.45 WARNING 200, Fire Mode
Cause
Fire mode has been activated.
Troubleshooting
The warning clears when fire mode is removed.
See the fire mode data in the alarm log.