VLT® HVAC Drive FC 131
Programming Guide
Perform a full AMA without filter only, while reduced AMA should be run with a filter.
4.3.4 1-3* Motor Data II
This parameter group comprises input data from the nameplate on the connected motor.
1-30 Stator Resistance (Rs)
Default value: Configuration dependent
Conversion index: -3
Set the stator resistance value. Enter the value from a motor datasheet or perform an AMA on a cold motor.
Table 53: Range:
Min: 0.0 Ohm
Max: 9999.000 Ohm
1-31 Rotor Resistance (Rr)
Default value: Configuration dependent
Conversion index: -3
Enter the rotor resistance value. Obtain the value from a motor data sheet or by performing an AMA on a cold motor. The default
setting is calculated by the drive from motor nameplate data.
Table 54: Range:
Min: 0
Max: 9999.000 Ohm
1-33 Stator Leakage Reactance (X1)
Default value: Configuration dependent
Conversion index: -3
Set the stator leakage reactance value. Enter the value from a motor data sheet or perform an AMA on a cold motor. The default
setting is calculated by the drive from motor nameplate data.
Table 55: Range:
Min: 0.0 Ohm
Max: 9999.000 Ohm
1-35 Main Reactance (Xh)
Default value: Configuration dependent
Conversion index: -2
Set the main reactance value. Enter the value from a motor data sheet or perform an AMA on a cold motor. The default setting is
calculated by the drive from motor nameplate data.
Table 56: Range:
Min: 0.0 Ohm
Max: 9999.00 Ohm
1-37 d-axis Inductance (Ld)
Default value: Configuration dependent
Conversion index: -3
Enter the value of the d-axis inductance. Obtain the value from the permanent magnet motor data sheet or perform an AMA on a
cold motor.
Danfoss A/S © 2022.05
N O T I C E
Parameter type: Range
Data type: u_int32
Default value: Configuration dependent
Parameter type: Range
Data type: u_int32
Default value: Configuration dependent
Parameter type: Range
Data type: u_int32
Default value: Configuration dependent
Parameter type: Range
Data type: u_int32
Default value: Configuration dependent
Parameter type: Range
Data type: int32
2-setup: All setups
Change during operation: False
2-setup: All setups
Change during operation: False
2-setup: All setups
Change during operation: False
2-setup: All setups
Change during operation: False
2-setup: All setups
Change during operation: False
AU370727746889en-000101 / 130R0994 | 51