VLT® HVAC Drive FC 131
Programming Guide
Table 239: Range:
Min: 0 s
14-22 Operation Mode
Default value: [0] Normal operation
Conversion index: -
To reset all parameter values to default, select [2] Initialisation.
Table 240: Option:
[0]
Normal op-
Select [0] Normal operation for normal operation of the drive with the motor in the selected application.
eration
[2]
Initialisation
Select [2] Initialisation to reset all parameter values to default settings, excluding bus communication param-
eters, parameter group 15-0* Operating Data, and parameter group 15-3* Alarm Log. The drive is reset during
the next power-up. Parameter 14-22 Operation Mode also reverts to the default setting [0] Normal operation.
14-23 Typecode Setting
Default value: 0
Conversion index: 0
Service use only.
Table 241: Range:
Min: 0
14-27 Action At Inverter Fault
Default value: [1] Warning
Conversion index: -
Select how the drive acts in the case of overvoltage, overcurrent, short circuit, or grounding errors.
Table 242: Option:
[0]
Trip
[1]
Warning
14-28 Production Settings
Default value: [0] No action
Conversion index: -
Service use only.
Table 243: Option:
[0]
[1]
[3]
Danfoss A/S © 2022.05
Max: 600 s
Parameter type: Option
Data type: u_int8
Parameter type: Range
Data type: u_int8
Max: 255
Parameter type: Option
Data type: u_int8
Disable the protection filters and trip at the 1
Run the protection filters normally.
Parameter type: Option
Data type: u_int8
No action
Service reset
Software reset
Default value: 10 s
2-setup: 1 setup
Change during operation: True
2-setup: 1 setup
Change during operation: False
Default value: 0
2-setup: All setups
Change during operation: True
st
fault.
2-setup: 1 setup
Change during operation: False
AU370727746889en-000101 / 130R0994 | 127