Danfoss VLT HVAC Drive FC 131 Programming Manual page 49

Hide thumbs Also See for VLT HVAC Drive FC 131:
Table of Contents

Advertisement

VLT® HVAC Drive FC 131
Programming Guide
[24]
[25]
[26]
[27]
[28]
[29]
[30]
[31]
[32]
1-22 Motor Voltage
Default value: Configuration dependent
Conversion index: -
Enter the nominal motor voltage according to the motor nameplate data. The default value corresponds to the nominal rated out-
put of the unit.
Table 47: Range:
Min: 50 V
Max: 1000 V
1-23 Motor Frequency
Default value: Configuration dependent
Conversion index: -
Select the motor frequency value from the motor nameplate data.
Table 48: Range:
Min: 20 Hz
Max: 400 Hz
1-24 Motor Current
Default value: Configuration dependent
Conversion index: -2
Enter the nominal motor current value from the motor nameplate data. This data is used for calculating motor torque, motor ther-
mal protection, and so on.
Table 49: Range:
Min: 0.01 A
Max: 1000.00 A
1-25 Motor Nominal Speed
Default value: Configuration dependent
Conversion index: -
Enter the nominal motor speed value from the motor nameplate data. This data is used for calculating automatic motor compensa-
tions.
Danfoss A/S © 2022.05
75 kW - 100 hp
90 kW - 120 hp
110 kW - 150 hp
132 kW - 180 hp
160 kW - 215 hp
200 kW - 270 hp
250 kW - 340 hp
315 kW - 425 hp
355 kW - 480 hp
Parameter type: Range
Data type: u_int16
Default value: Configuration dependent
Parameter type: Range
Data type: u_int16
Default value: Configuration dependent
Parameter type: Range
Data type: u_int32
Default value: Configuration dependent
Parameter type: Range
Data type: u_int16
2-setup: All setups
Change during operation: False
2-setup: All setups
Change during operation: False
2-setup: All setups
Change during operation: False
2-setup: All setups
Change during operation: False
AU370727746889en-000101 / 130R0994 | 49