VLT® HVAC Drive FC 131
Programming Guide
[168]
Drive in hand mode
[169]
Drive in auto mode
[188]
AHF capacitor connect
[190]
No-flow
[191]
Dry pump
[192]
End of curve
[193]
Sleep mode
[194]
Broken belt function
[196]
Fire mode
[198]
Drive bypass
6-73 Terminal 45 Output Min Scale
Default value: 0%
Conversion index: -2
Scale for the minimum output (0 mA or 4 mA) of the analog signal at terminal 45. Set the value to be the percentage of the full
range of the variable selected in parameter 6-71 Terminal 45 Analog Output.
Table 169: Range:
Min: 0%
6-74 Terminal 45 Output Max Scale
Default value: 100%
Conversion index: -2
Scale for the maximum output (20 mA) of the analog signal at terminal 45. Set the value to be the percentage of the full range of the
variable selected in parameter 6-71 Terminal 45 Analog Output.
Table 170: Range:
Min: 0%
6-76 Terminal 45 Output Bus Control
Default value: 0
Conversion index: 0
Holds the level of analog output if controlled by bus.
Table 171: Range:
Min: 0
4.8.5 6-9* Analog/Digital Output 42
Parameters for configuring the limits for analog/digital output terminal 42. Analog outputs are current outputs: 0/4–20 mA. Resolu-
tion on analog outputs is 12 bit. Analog output terminals can also be set up as digital output.
Danfoss A/S © 2022.05
Parameter type: Range
Data type: u_int16
Max: 200%
Parameter type: Range
Data type: u_int16
Max: 200%
Parameter type: Range
Data type: u_int16
Max: 16384
2-setup: All setups
Change during operation: True
Default value: 0%
2-setup: All setups
Change during operation: True
Default value: 100%
2-setup: All setups
Change during operation: True
Default value: 0
AU370727746889en-000101 / 130R0994 | 93
Parameters