Commissioning

5.4.2 Commissioning via [Main Menu]

Recommended parameter settings are intended for start-
up and checkout purposes. Application settings may vary.
Enter data with power ON, but before operating the
frequency converter.
1.
Press [Main Menu] on the LCP.
2.
Press the navigation keys to scroll to parameter
group 0-** Operation/Display and press [OK].
1107 RPM
Main menu
0 - ** Operation/Display
1 - ** Load/Motor
2 - ** Brakes
3 - ** Reference / Ramps
Illustration 5.2 Main Menu
3.
Press navigation keys to scroll to parameter
group 0-0* Basic Settings and press [OK].
0.0%
Operation / Display
0-0
*
Basic Settings
0-1
*
Set-up Operations
0-2
*
LCP Display
0-3
*
LCP Custom Readout
Illustration 5.3 Operation/Display
4.
Press navigation keys to scroll to 0-03 Regional
Settings and press [OK].
0.0%
Basic Settings
0-03 Regional Settings
[0] International
Illustration 5.4 Basic Settings
5.
Press navigation keys to select [0] International or
[1] North America as appropriate and press [OK].
(This changes the default settings for a number
of basic parameters).
6.
Press [Main Menu] on the LCP.
MG16E302
Operating Instructions
3.84 A
1 (1)
0.00A
1(1)
0-
**
0.00A
1(1)
0-0
*
Danfoss A/S © Rev. 2014-02-06 All rights reserved.
7.
Press the navigation keys to scroll to
0-01 Language.
8.
Select language and press [OK].
9.
If a jumper wire is in place between control
terminals 12 and 27, leave 5-12 Terminal 27 Digital
Input at factory default. Otherwise, select No
Operation in 5-12 Terminal 27 Digital Input.
10.
3-02 Minimum Reference
11.
3-03 Maximum Reference
12.
3-41 Ramp 1 Ramp Up Time
13.
3-42 Ramp 1 Ramp Down Time
14.
3-13 Reference Site. Linked to Hand/Auto Local
Remote.

5.4.3 Asynchronous Motor Set-up

Enter the motor data in parameter 1-20 Motor Power [kW]
or 1-21 Motor Power [HP] to 1-25 Motor Nominal Speed. The
information can be found on the motor nameplate.
1.
1-20 Motor Power [kW] or 1-21 Motor Power [HP]
2.
1-22 Motor Voltage
3.
1-23 Motor Frequency
4.
1-24 Motor Current
5.
1-25 Motor Nominal Speed

5.4.4 PM Motor Setup in VVC

NOTICE
Only use permanent magnet (PM) motor with fans and
pumps.
Initial Programming Steps
1.
Activate PM motor operation 1-10 Motor
Construction, select (1) PM, non salient SPM
2.
Set 0-02 Motor Speed Unit to [0] RPM
Programming motor data
After selecting PM motor in 1-10 Motor Construction, the
PM motor-related parameters in parameter groups 1-2*
Motor Data, 1-3* Adv. Motor Data and 1-4* are active.
The necessary data can be found on the motor nameplate
and in the motor data sheet.
Program the following parameters in the listed order
1.
1-24 Motor Current
2.
1-26 Motor Cont. Rated Torque
3.
1-25 Motor Nominal Speed
4.
1-39 Motor Poles
5
+
25
5