CD that is shipped with the It must be separately collected with electrical product, or in print at the local Danfoss sales office. and electronic waste according to local and currently valid legislation. MCT 10 Set-up Software Support Download the software from http://www.danfoss.com/...
Short circuit protection Danfoss recommends using the fuses and circuit breakers listed in Table 3.8 to protect service personnel or other equipment in case of an internal failure in the unit or short circuit on DC link.
Discharge from output phases to ground, using the value of Ground Fault – 15-31 Alarm Log Value if possible. Control Voltage – Fault Control voltage is low. Contact the local Danfoss supplier. 24 V supply low 24 V DC supply may be overloaded. AMA calibration – – failed Contact the local Danfoss supplier.
Page 47
The control card and power card are not matched. Illegal power – section configu- – ration Internal fault. Contact the local Danfoss supplier. Drive initialized – – All parameter settings are initialized to default settings. Auto DC Braking –...
The cooling capability of air is decreased at low air pressure. For altitudes above 2000 m (6562 ft), contact Danfoss regarding PELV. Below 1000 m (3281 ft) altitude, no derating is necessary. Above 1000 m (3281 ft), the ambient temperature or the maximum output current should be decreased.
Page 62
Danfoss shall not be responsible for any errors in catalogs, brochures or other printed material. Danfoss reserves the right to alter its products at any time without notice, provided that alterations to products already on order shall not require material changes in specifications previously agreed upon by Danfoss and the Purchaser. All trademarks in this material are property of the respective companies.