VLT® HVAC Drive FC 131
Programming Guide
View the calculated motor temperature in percentage of allowed maximum. At 100%, a trip occurs if selected in parameter 1-90
Motor Thermal Protection. The basis for the calculation is the ETR function selected in parameter 1-90 Motor Thermal Protection.
Table 306: Range:
Min: 0%
16-22 Torque [%]
Default value: 0%
Conversion index: 0
View the torque in percentage (in relation to the nominal torque) that is applied to the motor shaft.
Table 307: Range:
Min: -200%
16-26 Power Filtered [kW]
Default value: 0 kW
Conversion index: -3
Motor power consumption. The value shown is calculated on basis of the actual motor voltage and motor current. The value is
filtered, and a few seconds may pass from when an input value changes to when the data read-out values change.
Table 308: Range:
Min: 0 kW
16-27 Power Filtered [hp]
Default value: 0 hp
Conversion index: -3
Motor power in hp. The value shown is calculated on the basis of actual motor voltage and motor current. The value is filtered, and a
few seconds may pass from when an input value changes to when the data read-out values change.
Table 309: Range:
Min: 0 hp
4.13.3 16-3* Drive Status
16-30 DC Link Voltage
Default value: 0 V
Conversion index: 0
Show the actual DC-link voltage.
Table 310: Range:
Min: 0 V
16-34 Heatsink Temp.
Default value: 0 °C
Conversion index: 0
View the heat sink temperature of the drive.
142 | Danfoss A/S © 2022.05
Max: 100%
Parameter type: Range
Data type: int16
Max: 200%
Parameter type: Range
Data type: int32
Max: 1000 kW
Parameter type: Range
Data type: int32
Max: 1000 hp
Parameter type: Range
Data type: u_int32
Max: 65535 V
Parameter type: Range
Data type: int8
Default value: 0%
2-setup: All setups
Change during operation: False
Default value: 0%
2-setup: 1 setup
Change during operation: False
Default value: 0 kW
2-setup: 1 setup
Change during operation: False
Default value: 0 hp
2-setup: 1 setup
Change during operation: True
Default value: 0 V
2-setup: 1 setup
Change during operation: True