Danfoss VLT HVAC Drive FC 131 Programming Manual page 80

Hide thumbs Also See for VLT HVAC Drive FC 131:
Table of Contents

Advertisement

VLT® HVAC Drive FC 131
Programming Guide
5-34 On Delay, Digital Output
Default value: 0.01 s
Conversion index: -2
Enter the delay time before the digital output is switched on. The digital output (terminal 42/45) condition must not be interrupted
during the delay time.
Table 135: Range:
Min: 0 s
5-35 Off Delay, Digital Output
Default value: 0.01 s
Conversion index: -2
Enter the delay time before the digital output is switched off. The digital output (terminal 42/45) condition must not be interrupted
during the delay time.
Table 136: Range:
Min: 0 s
4.7.4 5-4* Relays
Parameters for configuring the timing and the output functions for the relays.
5-40 Function Relay
Default value: [0] No operation
Conversion index: -
Select options to define the function of the relays.
Table 137: Option:
[0]
No operation
[1]
Control Ready
[2]
Drive ready
[3]
Drive ready/remote
control
[4]
Standby / no warn-
ing
[5]
Drive running
[6]
Running / no warn-
ing
[7]
Run in range/no
warning
[8]
Run on ref/no warn-
ing
[9]
Alarm
[10]
Alarm or warning
80 | Danfoss A/S © 2022.05
Parameter type: Range
Data type: u_int16
Max: 600 s
Parameter type: Range
Data type: u_int16
Max: 600 s
Parameter type: Option
Data type: u_int8
No operation.
The control board receives supply voltage.
The drive is ready for operation and applies a supply signal on the control board.
The drive is ready for operation in auto-on mode.
The drive is ready for operation. No start or stop command is given. No warnings are present.
The motor runs.
The motor runs, and no warnings are present.
The motor runs within the programmed current ranges, see parameter 4-50 Warning Current Low
and parameter 4-51 Warning Current High. No warnings are present.
The motor runs at reference speed and with no warnings.
An alarm activates output.
An alarm or warning activates output.
2-setup: All setups
Change during operation: True
Default value: 0.01 s
2-setup: All setups
Change during operation: True
Default value: 0.01 s
2-setup: All setups
Change during operation: True
AU370727746889en-000101 / 130R0994
Parameters

Advertisement

Table of Contents
loading

Table of Contents