VLT® HVAC Drive FC 131
Programming Guide
Table 237: Range:
Min: 0
Max: 60000.000 ReferenceFeedbackUnit
4.11.3 14-2* Reset Functions
Parameters for configuring auto reset handling, special trip handling and control card self-test or initialization.
14-20 Reset Mode
Default value: [0] Manual reset
Conversion index: -
Define whether the drive waits for a manual reset, or resets itself automatically after tripping. In manual reset mode, press [RESET] or
use digital inputs to reset the drive.
In automatic reset mode, the motor can start without a warning.
Table 238: Option:
[0]
Manual reset
[1]
Automatic reset x 1
[2]
Automatic reset x 2
[3]
Automatic reset x 3
[4]
Automatic reset x 4
[5]
Automatic reset x 5
[6]
Automatic reset x 6
[7]
Automatic reset x 7
[8]
Automatic reset x 8
[9]
Automatic reset x 9
[10]
Automatic reset x 10
[11]
Automatic reset x 15
[12]
Automatic reset x 20
[13]
Infinite auto reset
14-21 Automatic Restart Time
Default value: 10 s
Conversion index: 0
To start the automatic reset function, enter the time interval from trip. This parameter is active when parameter 14-20 Reset Mode is
set to [1] - [13] Automatic reset.
A value of 0 s cannot be set when parameter 14-20 Reset Mode is set to option [13] Infinite auto reset.
126 | Danfoss A/S © 2022.05
Parameter type: Option
Data type: u_int8
N O T I C E
Select [0] Manual reset to reset the drive via [Reset] or via the digital inputs.
Select [1]-[12] Automatic reset x 1... x20 to perform between 1 and 20 automatic resets after trip-
ping.
Select [13] Infinite Automatic Reset for continuous resetting after tripping.
Parameter type: Range
Data type: u_int16
N O T I C E
Default value: 200.000 ReferenceFeedbackUnit
2-setup: All setups
Change during operation: True
2-setup: All setups
Change during operation: True
AU370727746889en-000101 / 130R0994
Parameters