Danfoss VLT HVAC Drive FC 131 Programming Manual page 185

Hide thumbs Also See for VLT HVAC Drive FC 131:
Table of Contents

Advertisement

VLT® HVAC Drive FC 131
Programming Guide
5.5.17 ALARM 38, Internal Fault
Cause
An internal fault occurs.
Troubleshooting
Contact your Danfoss supplier.
5.5.18 ALARM 44, Earth Fault II
Cause
There is a discharge from the output phases to ground, either in the cable between the drive and the motor or in the motor itself.
Troubleshooting
Turn off the drive and remove the ground fault.
Measure the resistance to ground of the motor cables and the motor with a megohmmeter to check for a ground fault in the
motor.
5.5.19 ALARM 46, Gate Drive Voltage Low
Cause
The supply on the power card is out of range. There are 3 supplies generated by the switch mode power supply (SMPS) on the
power card: 24 V, 5 V, and ±18 V.
Troubleshooting
Check the power card.
5.5.20 ALARM 47, 24 V Supply Low
Cause
The 24 V DC is measured on the control card. It occurs when the detected voltage on terminal 12 is lower than 18 V.
Troubleshooting
Check the control card and the load connected.
5.5.21 ALARM 51, AMA Check Unom and Inom
Cause
The settings for motor voltage, motor current, and motor power are wrong.
Troubleshooting
Check settings in parameters 1-20 to 1-25.
5.5.22 ALARM 52, AMA Low Inom
Cause
The motor current is too low.
Troubleshooting
Check the settings in parameter 1-24 Motor Current.
5.5.23 ALARM 53, AMA Motor Too Big
Cause
The motor is too big for the AMA to operate.
Troubleshooting
Check the settings in parameter group 1-2* Motor Data.
5.5.24 ALARM 54, AMA Motor Too Small
Cause
The motor is too small for the AMA to operate.
Troubleshooting
Check the settings in parameter group 1-2* Motor Data.
Danfoss A/S © 2022.05
Troubleshooting
AU370727746889en-000101 / 130R0994 | 185

Advertisement

Table of Contents
loading

Table of Contents