Danfoss VLT HVAC Drive FC 131 Programming Manual page 130

Hide thumbs Also See for VLT HVAC Drive FC 131:
Table of Contents

Advertisement

VLT® HVAC Drive FC 131
Programming Guide
14-52 Fan Control
Default value: [0] Auto
Conversion index: -
This parameter is used to select the fan control operating mode. The acoustic noise of the drive is different from running heavy load
(high heat sink temperature) to running light load or stand-by mode.
Table 253: Option:
[0]
Auto
The fan runs with full speed for a short time and then automatically adjusts the speed according to the
load and ambient temperature. The fan also runs at minimum speed even if the reference is 0 Hz due to
the heat generated from the IGBT. The fan stops if sleep mode function is activated.
[4]
Auto Low Temp
Only valid for I6-I8 enclosure sizes.
Env.
[5]
Constant-on
For on-site fan test or if the fan must run 100% speed constantly. Only valid for I2-I4 enclosure sizes.
mode
[6]
Constant-off
If convection cooling is sufficient or the drive is mounted in a demonstration panel, exhibitions and so
mode
on. The drive trips on heat sink overtemperature if loaded more than the convection cooling allows. Only
valid for I2-I4 enclosure sizes.
[7]
On-when-Inver-
The fan runs at maximum speed if in hand-on mode or reference is above 0 Hz. The fan is stopped if
ter-is-on-else-off
sleep mode is active. This is the default setting for H1 enclosure size only but can also be selected for I2-
Mode
I4 enclosure sizes.
14-53 Fan Monitor
Default value: [1] Warning
Conversion index: -
Select how the drive should react if a fan fault is detected. This parameter is only valid for drives of the following enclosure sizes:
IP54, 3x380–480 V, enclosure sizes I6–I8.
Table 254: Option:
[0]
[1]
[2]
14-55 Output Filter
Default value: [0] No Filter
Conversion index: -
Select the type of connected output filter.
Table 255: Option:
[0]
No Filter
[1]
Sine-Wave Filter
[3]
Sine-Wave Filter with Feedback
[4]
dU/dt
130 | Danfoss A/S © 2022.05
Parameter type: Option
Data type: u_int8
Parameter type: Option
Data type: u_int8
Disabled
Warning
Trip
Parameter type: Option
Data type: u_int8
No filter is selected.
For backwards compatibility only.
Sine-wave filter with feedback is selected.
This option is only valid for drives of the following enclosure sizes:
IP54, 3x380–480 V, enclosure sizes I6–I8.
2-setup: 1 setup
Change during operation: True
2-setup: 1 setup
Change during operation: True
2-setup: 1 setup
Change during operation: False
AU370727746889en-000101 / 130R0994